According to the project and details,

  • Double spacing Aypan DU profiles (galvanized steel sheet in accordance with TS EN 14195) should be fixed to the base and ceiling by using Aypan screws and plastic dowels at 60 cm intervals, leaving an intermediate space.
  • Aypan sound insulation tape should be affixed behind the Aypan DC profiles (made in accordance with TS EN 1495) to be attached to DU and side walls.
  • The DC profiles should be dimensioned according to the wall height (cut if necessary). The DC profiles should be inserted between the two DU profile lines at 40 or 60 cm intervals to form a double frame.
  • If desired, rockwool plates of appropriate thickness and density should be placed between the DC profiles.
  • Aypan should be cut and dimensioned and the first layer should be fixed to the profiles with 25 mm and the second layer 35 mm.
  • This should be done in the same way on the other side of the wall.
  • Aygips joint filler plaster should be pre-filled into gaps more than 3mm.
  • Screw heads should be covered with Aygips grouting plaster.
  • Joint tape should be adhered to Aypan joints.
  • A partition wall should be formed by applying Aygips joint filler plaster on the joint tape.

All kinds of materials and losses, workplace loading, horizontal and vertical transport, unloading and contractor profit and general expenses, including 1 m2 price.

Quantities

Prodoct Code Material Name 40 cm** 60 cm** Unit
AL125BY250 AYPAN (12,5 mm) 4,00 4,00
AK50NDC300 AYPAN DC50 Profil  5,60 4,00 m
AK50NDU300 AYPAN DU50 Profil 1,60 1,60 m
BN050YB025 AYPAN Ses İzolasyon Bandı 2,60 2,60 m
AB048DV145 AYPAN Vida ve Plastik Dübel Seti 4,40 4,40 pcs
AB035BV025 AYPAN Sivri Uçlu Vida 3,5x25 mm  38,00 30,00 pcs
AB035BV035 AYPAN Sivri Uçlu Vida 3,5x35 mm  38,00 30,00 pcs
BN050DB090 AYPAN Derz Bandı 2,80 2,80 m
AG001DD025 AYGIPS Alçı Levha Derz Dolgu Alçısı 0,80 0,80 kg
  Taş Yünü 1,00 1,00
 
AG001ST025 AYGIPS Saten Perdah Alçısı For each one mm kg
AK022DP270 AYPAN Delikli Köşe Profili As per project m
            
A DOOR SYSTEM ANALYZE
Material Name Quantities Unit
Door Supported Stud    
L Bracket Somun Bolt Set    
Steel anchor    
*Without wastage  
**DC Profile axis gap
***Ask to technical office for choosing different sizes profiles.  
***Based on 4X2,5 mt wall measurements.

Performance

Non-carrier partition wall system. It is formed by screwing two layers of Aypan on both sides of the double metal frame (Aypan DC) made of galvanized steel sheet.

·It can be used in all kinds of buildings such as office, hospital, hotel, residence where more sound and fire resistance performance is required than 1TP22 and wider wiring is required. max. It can be applied up to 6.50 m height.

·The average weight of the system is 56-60 kg / m2.

·Fire resistance Aypan® White with F 60, Aypan® Red with F90 `is.

·To improve the sound and heat performance of the system, insulation boards such as rock wool can be placed between the profiles. Sound insulation performance is between 60-63 dB in high soundproof system.

·Aypan Sound Insulation Tape should be adhered to the profile backs on the surfaces where the flooring and wall intersect, and measures should be taken against sound bridges.

·The gap between the profiles can be used as the installation passage.